Dyness
Dyness Tower T10
Single-phase off grid inverter with 10.127 kWh LFP battery
Partially verified
Best for
- + Residential installations
- + Single-phase residential installations
- + Projects requiring long warranty coverage
- + LFP battery applications - verify cycle life from datasheet
Not ideal for
- ! Large-scale C&I projects - consider commercial product line
- ! Three-phase commercial/industrial installations
- ! Backup/battery-backup projects (no EPS functionality)
In the Tower series
This is the 10.127 kWh variant.
Compared to other models
- - 50% larger capacity than Dyness Tower T7
- - 50% smaller capacity than Dyness Tower T21
- - Mid-range option balancing capacity and project flexibility.
Ideal for
Ideal for installers who need a balanced 10.127 kWh option with 6.39 kW for mainstream project sizing.
Key Specifications
Usable Capacity
10.127 kWh
VendorShow All Specifications
Batterie
| Batteriechemie | LFPVendor |
| Batteriespannungsklasse | HVVendor |
| Kapazitaet (Nominal) | 10.66 kWhVendor |
| Kapazitaet (Nutzbar) | 10.127 kWhVendor |
| Nennspannung | 288 VVendor |
| Spannungsbereich | 252 ~ 328 VVendor |
| Min. Module | 2Vendor |
| Max. Module | 6Vendor |
| Installationsart | -Vendor |
| Skalierbare Kapazitaet Min | 10.66 kWhVendor |
| Skalierbare Kapazitaet Max | 255.72 kWhVendor |
| Max. Ladeleistung | 6.39 kWVendor |
| Max. Entladeleistung | 6.39 kWVendor |
| Spitzen-Entladeleistung | 6.39 kWVendor |
| Zyklenlebensdauer | 6000 cyclesVendor |
| DoD | 95 %Vendor |
| Rundlaufwirkungsgrad | 95 %Vendor |
Umgebung & Mechanik
| IP-Schutzart | IP54Vendor |
| Ladetemperaturbereich | 0 ~ 50Vendor |
| Entladetemperaturbereich | -10 ~ 50Vendor |
| Heizung unterstützt | falseVendor |
| Abmessungen (B x H x T) | 504*380*900 mmVendor |
| Gewicht | 146 kgVendor |
EMS & Kommunikation
| BMS-Schnittstellen | CAN / RS485Vendor |
| Kompatible Wechselrichter | Kostal, Goodwe, Solis, Deye, Solplanet, Solinteg, Sunways, SAJ, Sinexcel, Hoymiles, Growatt, ATESS, Sineng, etc.Vendor |
| BMS-Update unterstützt | trueVendor |
Konformitaet & Garantie
| Zertifizierungen | UN38.3, CE-EMC, IEC62040, IEC62619, IEC62477, IEC60730, IEC63056, UKCA, CEC Accredited, UL1973, VDE2510-50Vendor |
| Transportzertifizierungen | UN38.3Vendor |
Data Confidence & Verification
Partially verifiedData Sources
- + Official datasheet - verified 2026-04-27
- - Installation Manual - not available
- - Certificate - not available
Data gaps that may affect your decision
- ! Outdoor temperature range not specified - confirm outdoor suitability.
- ! IP rating not documented - confirm installation location suitability.
Quick Check: Does this product fit your project?
Run a single-product scenario check using the same Product Match rules.
Compliance & Certifications
No compliance data available for this product.
Certifications
-
Documents & Downloads
DATASHEET PDF
- Dyness Tower T10 DatasheetDownload
Compatible Products - coming in Phase 3
Product data is sourced from manufacturers, official websites, and community contributions. Energidea does not guarantee completeness or accuracy. Installers should verify specifications, certifications, and compatibility with manufacturer documentation before quotation.
Kernfelder für Vergleich sind unvollständig (>30% fehlen). Direkter Vergleich wird nicht empfohlen.
Installateur-AI-Prompt
Erstellen Sie installateurgerechte Prompt-Vorlagen für ChatGPT oder Gemini.